Residual current monitoring strategy: Where should measurements be taken?
The guide illustrates this model's “Six-channel monitoring of final circuits” function with a product example.
Read the technical guideAC/DC-sensitive residual current monitoring series with six integrated measuring current transformers.
AC/DC-sensitive residual current monitoring series with six integrated measuring current transformers. When selecting, consider nominal values, supply options and required system components together.
Bender official product source ↗The RCMS150 series provides six-channel Type B monitoring with RMS and DC evaluation per channel. RCMS150 uses BMS over RS-485; RCMS150-01 uses Modbus RTU. Exact variant selection must match the existing monitoring system’s protocol.
| Measurement coverage | Residual current up to 500 mA, DC…2 kHz |
| Circuit specified in the document | 300 V, 32 A; conductor insulation conditions require separate evaluation at higher voltages |
| Measurement channels | 6 channels; RMS and DC evaluation on each channel |
Explore the product's function and its system's operating principle through technical explanations.
The guide illustrates this model's “Six-channel monitoring of final circuits” function with a product example.
Read the technical guideLearn the difference between residual current measurement/alarm and tripping for protection.
Read the technical guideReview AC, pulsating DC and smooth DC detection coverage together with sensor and model selection.
Read the technical guideTechnical product information and supply support for model selection, compatible components and current manufacturer documentation.
Assess the option for your application using model names, order codes and technical values. Accessories appear in separate tables.
7 / 7 options
No options match your search. Change the model name or order code.
| Model | Rated supply voltage U s | Protocol | Order code |
|---|---|---|---|
| RCMS150 | DC 24 V | BMS | B94053025 |
| RCMS150-01 | DC 24 V | Modbus RTU | B94053026 |
| RCMS150-W-01 | DC 24 V | Modbus RTU | B94053026W |
| Description | RCMS150 | RCMS150-01 | Model | Order code |
|---|---|---|---|---|
| Mounting clip for DIN rail mounting | ✓ | ✓ | B91080110 | |
| Condition Monitor with integrated gateway | ✓ | ✓ | COM465IP / CP907-I (flush-mounted enclosure) / CP907-I (control cabinet door mounting) | B95061065 / B95061031 / B95061032 |
| RS-485 repeater | ✓ | ✓ | DI-1DL | B95012047 |
| Residual current monitoring system* | ✓ | - | RCMS460-D-1 / RCMS460-D-2 / RCMS490-D-1 / RCMS490-D-2 | B94053001 / B94053002 / B94053005 / B94053006 |
* In this case, no condition monitor/gateway is necessary. Suitable for measured-value and alarm indication only; not suitable for parameter setting.
Based on tables on the manufacturer's current product page. For marked-value footnotes, connection conditions and variant suitability, review Bender product source ↗ and the technical documents together. Listing an order code does not commit to stock availability or delivery time.
Find product and accessory documents by type or file name. Language and file information appear beside each document.
4 / 4 documents
No documents match your search. Change the search or document type.
Data sheets and operating manuals open Bender’s official PDFs in a new tab. Documents are in English.
Other languages, accessory documents and current revisions · Bender ↗
Data sheets, operating manuals and related manufacturer documents. File names identify the model or accessory; documents retain their original language.
ADEO Teknik · Bender's distributor in Türkiye. Current Bender product source ↗
Contact your distributor in Türkiye for product selection, technical documents and quotations.