What is insulation monitoring of de-energised circuits?
The guide illustrates this model's “Offline monitoring of standby motors and pumps” function with a product example.
Read the technical guideOffline monitoring device for the insulation resistance of de-energised standby loads in TN, TT and IT systems.
Monitoring de-energised loads
Explore the product's function and its system's operating principle through technical explanations.
The guide illustrates this model's “Offline monitoring of standby motors and pumps” function with a product example.
Read the technical guideCompare the different purposes of equipment testing, spot measurement and continuous monitoring.
Read the technical guideTechnical product information and supply support for model selection, compatible components and current manufacturer documentation.
Assess the option for your application using model names, order codes and technical values. Accessories appear in separate tables.
7 / 7 options
No options match your search. Change the model name or order code.
| Model | Supply voltage* U S | Alarm threshold R an | System leakage capacitance C e | Order code** |
|---|---|---|---|---|
| IR420-D6-1 | DC 9,6…94 V / / AC 16…72 V, 42…460 Hz | 100 kΩ…10 MΩ | ≤ 10 µF | B71016415 / B91016415 |
| IR420-D6-2 | DC 70…300 V / / AC 70…300 V, 42…460 Hz | 100 kΩ…10 MΩ | ≤ 10 µF | B71016407 / B91016407 |
* Absolute values **(B7… = push-wire terminal / B9… = screw-type terminal)
| Model | Nominal system voltage* U n | Order code |
|---|---|---|
| AGH150W | AC 0…1150 V, DC 0…1100 V | B915576 |
| AGH204S-4 | AC 0…1650 V / AC + DC 0…1300 V | B914013 |
| AGH520S | AC 0…7200 V, 50…400 Hz | B913033 |
| Mounting clip for screw mounting (1 piece per device) | B98060008 | |
| Mounting frame XM420 | B990994 |
Based on tables on the manufacturer's current product page. For marked-value footnotes, connection conditions and variant suitability, review Bender product source ↗ and the technical documents together. Listing an order code does not commit to stock availability or delivery time.
Find product and accessory documents by type or file name. Language and file information appear beside each document.
4 / 4 documents
No documents match your search. Change the search or document type.
This summary is based on product descriptions and features on the specified pages of the documents above. Consult the manufacturer document for complete technical values, connection information and ordering options.
Current product and variant information · Bender ↗
Data sheets, operating manuals and related manufacturer documents. File names identify the model or accessory; documents retain their original language.
ADEO Teknik · Bender's distributor in Türkiye. Current Bender product source ↗
Used for standby loads such as fire pumps, emergency drives, valve motors and standby generators. It gives a prewarning when insulation deteriorates and supports preventing a faulty load from starting through a suitable external interlock circuit.
Contact your distributor in Türkiye for product selection, technical documents and quotations.